Brainchild BTC-9300 Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Nie Brainchild BTC-9300. Brainchild BTC-9300 User`s manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 142
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
User's ManualUser's Manual
BTC-9300
Self-Tune Fuzzy / PID
Process / Temperature Controller
BTC-9300
Self-Tune
Fuzzy / PID
Process
/ Temperature Controller
UM93001G
Przeglądanie stron 0
1 2 3 4 5 6 ... 141 142

Podsumowanie treści

Strona 1 - UM93001G

User's ManualUser's ManualBTC-9300Self-Tune Fuzzy / PIDProcess / Temperature ControllerBTC-9300Self-TuneFuzzy / PIDProcess/ Temperature Cont

Strona 2 - Use the ManualUse the Manual

BTC-9300A1 A2 PVCFSVOUTBTC-9300Power OnPower OnAll segments of display andindicators are left off for 0.5second.All segments of display andindicatorsa

Strona 3 - CONTENTS

Chapter 6 CalibrationChapter 6 CalibrationDo not proceed through this section unless there is a definite need tore-calibrate the controller. Otherwise

Strona 4 - 1 1 Features1 1 Features

Press scroll key until the display shows . Send a 60mV signalto terminals 12 and 13 in correct polarity . Press scroll key for atleast 3 seconds . The

Strona 5

Stay at least minutes in still-air roomroom temperature 25 3 C20ALStay at least minutes in still-airroomroomtemperature 25 3 C20ALPerform step 10 to c

Strona 6

Perform step 1 stated above , then press scroll key until the displayshows . Apply up/down key until value 0.0 is obtained. Pressscroll key for at lea

Strona 7

BTC-9300A1SVOUTA2 PV FCChapter 7 Error Codes & TroubleshootingChapter 7 Error Codes & TroubleshootingUM93001C104This procedure requires access

Strona 8 - Access Hole

UM93001C105Table 7.1 Error Codes and Corrective ActionsTable 7.1 Error Codes and Corrective ActionsErrorCodeDisplaySymbolError DescriptionCorrective A

Strona 9

Table 7.2 Common Failure Causes and Corrective ActionsTable 7.2 Common Failure Causes and Corrective ActionsSymptomProbable Causes Corrective Actions1

Strona 10 - Power OnPower On

Chapter 8 SpecificationsChapter 8 SpecificationsPowerInput 1Input 1Input 2Input 2Input 3 (Event Input )Input 3 (Event Input )90 264 VAC, 47 63 Hz, 15V

Strona 11

UM93001DTriac ( SSR ) OutputTriac ( SSR ) OutputRating :Inrush Current :Min. Load Current :Max. Off-state Leakage :Max. On-state Voltage :Insulation R

Strona 12 - Mode Priority

Environmental & PhysicalEnvironmental & PhysicalOperating Temperature :Storage Temperature :Humidity :Insulation Resistance :Dielectric Streng

Strona 13 - Basic Function Mode

PV ValueSV ValueUserMenuUserMenuSetupMenuSetupMenuHand (Manual)ControlModeHand (Manual)ControlModeAuto-tuningModeAuto-tuningModeDisplayModeDisplayMode

Strona 14

UM93001GChapter 9 Modbus CommunicationsChapter 9 Modbus CommunicationsThis chapter specifies the Modbus Communications protocol as RS-232 or RS-485 in

Strona 15

UM93001GException CodeNameCause1Bad function codeFunction code is not supported by the controllerIllegal data addressIllegal data valueRegister addres

Strona 16

UM93001GParameterNotationRegisterAddressParameter DescriptionDataTypeRangeLowHighHigh01234567891011121314151617181920212223242526272829303132333435363

Strona 17

UM93001GParameterNotationRegisterAddressParameter Description40414243444546474849505152535455565758596061626364656667686970717273747576777879SP1LSP1HI

Strona 18

UM93001GParameterNotationRegisterAddressParameter Description80818283848586878889909192939495969798991001011021031041051061071081091101111121131141151

Strona 19

UM93001GParameterNotationRegisterAddressParameter Description120121122123124125126127128129130131132PVHIPVLOPVSVMV1MV2ALMFILELow LowHigh HighDataTypeD

Strona 20

UM93001G*A: R/W Specifies a readable / writable data, R specifies a read onlydata.*A1: The communication setup data which can't be modified viaco

Strona 21 - 2 1 Unpacking2 1 Unpacking

UM93001G*B13, Display symbol and description for IN1U & IN2U*B14, Display symbol and description for DP1 & DP2ParameterValueParameterValueDisp

Strona 22 - 0.08" max

UM93001G*B22, Display symbol and description for A1FN & A2FN*B21, Display symbol and description for DISFParameterValueDisplaySymbolDescription01P

Strona 23 - Supply Connections

UM93001G*B30, Display symbol and description for SPMDParameterValueDisplaySymbolDescription012345SP1.2MIN.RHR.RPV1PV2PUMPUse SP1 or SP2 (depends on EI

Strona 24

1 6 System Modes1 6 System ModesThe controller performs close loop control under its normal control mode condition.The controller will maintain its no

Strona 25

UM93001GErrorCodeDisplaySymbolError DescriptionCorrective ActionCommunication error:receive error due toparity error, framingerror, overrun error,rece

Strona 26

UM93001G*B36, Display symbol and description for MODEInput 2 ( IN2 ) sensorbreak, or input 2current below 1 mA if4-20 mA is selected, orinput 2 voltag

Strona 27

UM93001G*C: The parameters are preset with the default values specified in the table during production.the value of the parameter = LS+Rx65535(HS LS)6

Strona 28 - DIN RailDIN Rail

UM93001GExample 1: Preset 9 multiple registersExample 1: Preset 9 multiple registers9 4 Communication Examples9 4 Communication Examples01 101800 0052

Strona 29

UM93001GA 1 Menu Existence CoditionsA 1 Menu Existence CoditionsMenu Existence Conditions TableMenu Existence Conditions TableMenuParameterNotationPar

Strona 30

UM93001GMenuParameterNotationParameterNotationExists unconditionallyExists unconditionallyFUNCExists if FUNC selects FULLExists if FUNC selects FULLEx

Strona 31 - Mains Supply

MenuParameterNotationParameterNotationExists unconditionallyExists unconditionallyExists unconditionallyExists unconditionallyExists if A1FN is not NO

Strona 32

Parameter DescriptionParameter DescriptionRangeDefaultValueDefaultValueParameterNotationParameterNotationDisplayFormatDisplayFormatCurrent Error CodeA

Strona 33

RangeDefaultValueDefaultValueHOURHRLOERR1ERR2DELIBPL1BPL2Working Hour ValueFractional Hour ValueHistorical Error Record 1Historical Error Record 2ASCI

Strona 34

A 3 GlossaryA 3 GlossaryAbosolute zero: The lowest theoretical temperature. Atabsolute zero, a body would have no molecular motionof heat energy. Abso

Strona 35

1 7 Parameter Description1 7 Parameter DescriptionTable 1.4 Parameter DescriptionTable 1.4 Parameter DescriptionParameterDescriptionParameterDescripti

Strona 36 - 2 15 RS-4852 15 RS-485

Celsius: (Centigrade) A temperature scale with 0 Cdefined as the ice point and 100 C as the boiling pointof water at sea level.Celsius: (Centigrade) A

Strona 37 - 2 16 RS-2322 16 RS-232

emf: Electromotive force. A rise in (electrical) potentialenergy. The principal unit is the volt.emf: Electromotive force. A rise in (electrical) pote

Strona 38

Junction: A thermocouple junction is the point at whichtwo alloys are joined. A typical thermocouple circuitwould have a measuring and a reference jun

Strona 39 - Calibrator

Proportional control mode: When process temperatureapproaches set point and enters the proportional band,the output is switched on and off at the esta

Strona 40 - 3 1 Input 13 1 Input 1

UM93001G134RFI: Radio frequency interference.RFI: Radio frequency interference.RS232 or RS485 output signal: A serial interface suitablefor connection

Strona 41

Volt: The (electrical) potential difference between twopoints in a circuit. The fundamental unit is derived aswork per unit charge (V=W/Q). One volt i

Strona 42 - UM93001D

UM93001G136A 4 IndexA 4 IndexA1DV: 11, 13, 18, 47, 48, 50, 51, 5354, 110A1FN: 11, 16, 17, 20, 42, 43, 47, 48,49, 50, 51, 52, 53, 54, 56, 70, 71,72, 83

Strona 43 - ON-OFF Control

UM93001G137FILT: 11, 17, 40, 78, 80, 81, 83, 108Flow: 4, 11, 61, 62Freezer: 54, 88, 90FUNC: 9, 11, 13, 40, 73, 74, 76, 77,79, 80, 83, 86, 87, 89, 92,

Strona 44 - Figure 3.3 Cool Only

UM93001G138PVHI: 9, 11, 19, 66PV1: 11, 13, 17, 19, 20, 40, 41, 45,48, 49, 55, 56, 66, 70, 73, 74, 77,78, 80, 83, 92, 93, 94, 95, 99, 105,108PV1 shift:

Strona 45

UM93001G139A5MemoA 5 MemoUse the following Table as a master copy for your settings.Use the following Table as a master copy for your settings.SP1TIME

Strona 46

ParameterDescriptionParameterDescriptionRangeDefaultValueDefaultValueContainedinContainedinBasicFunctionBasicFunctionParameterNotationParameterNotatio

Strona 47

UM93001GOUT2O2TYCYC2O2FTA1FNA1MDA1FTA2FTA2FNA2MDEIFNSELFSLEPPVMDFILTSP2FSPMDSEL1SEL2SEL3SEL4SP1LSP1HSEL5AD0ADGV1GCJTLMA2GV2GCJGREF1SR1MA1GPVHIPVLOMV1M

Strona 48

A 6 WarrantyA 6 WarrantyWARRANTYRETURNSNo products return can be accepted without a completed Return Material Authorization ( RMA ) form.No products r

Strona 49

No.209, Chung Yang Rd., Nan Kang Dist., Taipei, Taiwan, R.O.C.Tel: 886-2-27861299Fax: 886-2-27861395web site: http://www.brainchild.com.twNo.209, Chun

Strona 50

Low:Low:High:High:IN2UDP2IN2LIN2HIN2 Unit SelectionIN2 Decimal Point SelectionIN2 Low Scale ValueIN2 High Scale Value-19999-199994553645536Same as IN1

Strona 51

ParameterDescriptionParameterDescriptionRangeDefaultValueDefaultValueContainedinContainedinBasicFunctionBasicFunctionParameterNotationParameterNotatio

Strona 52 - Break Alarm

ParameterDescriptionParameterDescriptionRangeDefaultValueDefaultValueContainedinContainedinBasicFunctionBasicFunctionParameterNotationParameterNotatio

Strona 53 - Break Sources

SP2FFormat of set point 2 Value01set point 2 (SP2) is an actual valueset point 2 (SP2) is a deviationvalue0ParameterDescriptionParameterDescriptionRan

Strona 54 - 314SP1Range3 14 SP1 Range

ParameterDescriptionParameterDescriptionRangeDefaultValueDefaultValueContainedinContainedinBasicFunctionBasicFunctionParameterNotationParameterNotatio

Strona 55 - 315PV1Shift3 15 PV1 Shift

2UM93001CWarning SymbolWarning SymbolUse the ManualUse the ManualThe Symbol calls attention to an operating procedure, practice, or the like, which, i

Strona 56

Table 1.5 Input ( IN1 or IN2 ) RangeTable 1.5 Input ( IN1 or IN2 ) RangeTable 1.6 Range Determination for A1SPTable 1.6 Range Determination for A1SPTa

Strona 57

Chapter 2 InstallationChapter 2 Installation2 2 Mounting2 2 Mounting2 1 Unpacking2 1 UnpackingUpon receipt of the shipment remove the unit from the ca

Strona 58

2 3 Wiring Precautions2 3 Wiring PrecautionsBefore wiring, verify the label for correct model number and options. Switchoff the power while checking.C

Strona 59 - Procedures:

2 4 Power Wiring2 4 Power Wiring19210311412513614715816The controller is supplied to operate at 11-26 VAC / VDC or 90-264VAC.Checkthat the installatio

Strona 60

2 5 Sensor Installation Guidelines2 5 Sensor Installation GuidelinesProper sensor installation can eliminate many problems in a control system. Thepro

Strona 61

2 6 Thermocouple Input Wiring2 6 Thermocouple Input Wiring19210311412513614715816+Figure 2.5Thermocouple Input WiringFigure 2.5ThermocoupleInput Wirin

Strona 62

2 7 RTD Input Wiring2 7 RTD Input Wiring2 8 Linear DC Input Wiring2 8 Linear DC Input WiringFigure 2.6RTD Input WiringFigure 2.6RTDInput WiringDC line

Strona 63

Figure 2.9Input 2 Linear Voltage WiringFigure 2.9Input2 Linear Voltage WiringFigure 2.10Input 2 Linear Current WiringFigure 2.10Input2 Linear Current

Strona 64

2 9 CT / Heater Current Input Wiring2 9 CT / Heater Current Input WiringCT94 112++DIN RailDIN Rail19210311412513614715816FuseMainssupplyMainssupplyHea

Strona 65 - Exception

2 10 Event Input wiring2 10 Event Input wiringOpen CollectorInputOpen CollectorInputSwitch InputSwitch Input+19210311412513614715816192103114125136147

Strona 66

3UM93001GCONTENTSChapter 1 OverviewChapter 1 Overview1-1 Features1-2 Ordering Code1-3 Programming Port and DIP Switch1-4 Keys and Displays1-5 Menu Ove

Strona 67 - Operation

2 11 Output 1 Wiring2 11 Output 1 Wiring19210311412513614715816120V/240VMains Supply120V/240VMainsSupplyMax. 2AResistiveMax. 2AResistiveLoadRelay Outp

Strona 68 - Terminals:

192103114125136147158160-1V, 0-5V1-5V,0-10V0 - 1V, 0 - 5V1- 5V, 0 - 10VLinear VoltageLinear Voltage19210311412513614715816Linear CurrentLinear Current

Strona 69 - Availability

2 12 Output 2 Wiring2 12 Output 2 Wiring19210311412513614715816120V/240VMains Supply120V/240VMainsSupplyMax. 2AResistiveMax. 2AResistiveLoadRelay Outp

Strona 70

Linear VoltageLinear VoltageLinear CurrentLinear CurrentMaximum Load 500 ohmsMaximum Load 500 ohmsMinimum Load 10 K ohmsMinimum Load 10 K ohms19210311

Strona 71

2 13 Alarm 1 Wiring2 13 Alarm 1 Wiring19210311412513614715816120V/240VMains Supply120V/240VMainsSupplyMax. 2AResistiveMax. 2AResistiveLoadRelay Output

Strona 72

2 14 Alarm 2 Wiring2 14 Alarm 2 Wiring19210311412513614715816120V/240VMains Supply120V/240VMainsSupplyMax. 2AResistiveMax. 2AResistiveLoadRelay Output

Strona 73 - Error MessageError Message

2 15 RS-4852 15 RS-485192103114125136147158161921031141251361471581619210311412513614715816TX1TX1TX1TX1TX2TX2TX2TX2Terminator220 ohms / 0.5WTerminator

Strona 74

2 16 RS-2322 16 RS-23219210311412513614715816TX1 TX2Note:If the BTC-9300 is configured for RS-232 communication, the EI ( EventInput ) is disconnected

Strona 75

2 17 Analog Retransmission2 17 Analog Retransmission1921031141251361471581619210311412513614715816++++++++LoadLoadLoadLoadLoadLoad0-20mA,4-20mA0 - 20m

Strona 76

2 18 Programming Port2 18 Programming PortSee Figure 1.3 in Section 1-3 to find the programming port location.See Figure 1.3 in Section 1-3 to find th

Strona 77

Chapter 1 OverviewChapter 1 Overview1 1 Features1 1 FeaturesBTC-9300 Fuzzy Logic plus PID microprocessor-based controller, incorporates a bright,easy

Strona 78

This unit provides an useful parameter " FUNC " which can be used to selectthe function complexity level before setup. If the Basic Mode ( F

Strona 79 - Setup MenuSetup Menu

IN1LIN1HIN1L : Selects the low scale value for the Linear type input 1.T/C or RTD type is selected for IN1.Hidden if :IN1L : Selects the low scale val

Strona 80

3 3 Rearrange User Menu3 3 Rearrange User MenuThe conventional controllers are designed with a fixed parameters' scrolling. Ifyou need a more fri

Strona 81

3 4 Heat Only Control3 4 Heat Only ControlHeat Only ON-OFF Control : Select REVR for OUT1, Set PB1 to 0, SP1 is usedto adjust set point value, O1HY is

Strona 82 - BTC-9300

3 5 Cool Only Control3 5 Cool Only ControlON-OFF control,P(PD)control and PID control can be used for cool control.Set OUT1 to DIRT ( direct action ).

Strona 83 - Key menu:Key menu:

3 6 Heat-Cool Control3 6 Heat-Cool ControlThe Heat-Cool Control can use one of combinations of control modes. Setup of parameters for each controlmode

Strona 84

46UM93001DCPB Programming : The cooling proportional band is measured by % of PB with range 1~255. Initially set 100% forCPB and examine the cooling e

Strona 85

3 7 Dwell Timer3 7 Dwell TimerSP1PVTimeONOFFA1 or A2TimeTimeTIMETimer startsFigure 3.4 Dwell Timer FunctionFigure 3.4 Dwell Timer FunctionIf alarm 1 i

Strona 86

3 8 Process Alarms3 8 Process AlarmsThere are at most two independent alarms available by adjusting OUT2. If=AL2 is selected for OUT2, then OUT2 will

Strona 87

205195205195205205205195195195ONFigure 3.6Latching Process AlarmFigure 3.6LatchingProcess AlarmA1SP = 200 A1HY = 10.0A1MD = LTCH A1FN = PV1.HA1SP = 20

Strona 88

In last nearly a hundred years although PID control has been used and proved to be anefficient controlling method by many industries, yet the PID is d

Strona 89 - Key MenuKey Menu

3 9 Deviation Alarm3 9 Deviation AlarmA1FN = DE.HI, A1MD = NORM, SP1 = 100, A1DV=10, A1HY=4A1FN = DE.HI, A1MD = NORM, SP1 = 100, A1DV=10, A1HY=4A1FN =

Strona 90

3 10 Deviation Band Alarm3 10 Deviation Band AlarmExamples:9595959595959595959595959595959595100100100100100100100100100100100100100100100100100105105

Strona 91

3 11 Heater Break Alarm3 11 Heater Break AlarmA current transformer ( parts No. ) should be installed to detect theheater current if a heater break al

Strona 92 - Figure 5.12Figure 5.12

3 12 Loop Break Alarm3 12 Loop Break AlarmA1FN selects LB if alarm 1 is required to act as a loop break alarm. Similarly, ifalarm 2 is required to act

Strona 93

314SP1Range3 14 SP1 Range3 13 Sensor Break Alarm3 13 Sensor Break AlarmSP1L ( SP1 low limit value ) and SP1H ( SP1 high limit value ) in setup menuare

Strona 94 - Figure 5.15Figure 5.15

315PV1Shift3 15 PV1 Shift165 CCHeatTransfer200 CSensorSubjectHeater35 C temperaturedifference is observedSHIF= 0165 CCHeatTransfer200 CSensorSubjectHe

Strona 95 - Figure 5.16Figure 5.16

3 16 Failure Transfer3 16 Failure TransferThe controller will enter as one of the following conditions occurs:1. occurs ( due to the input 1 sensor br

Strona 96 - 5 10 RS-4855 10 RS-485

3 17 Bumpless Transfer3 17 Bumpless TransferThe bumpless transfer function is available for output 1 and output 2 ( providedthat OUT2 is configured as

Strona 97 - Setup Setup MenuSetup Menu

3 18 Self tuning3 18 Self tuningSelf-tune MenuSelf-tune MenuSelectsDisable Self-tuningDisable Self-tuningEnable Self-tuningEnable Self-tuningor58UM930

Strona 98 - 5 11 RS-2325 11 RS-232

3 19 Auto tuning3 19 Auto tuningThe auto-tuning process is performed at set point.The process will oscillate around the set point during tuning proces

Strona 99 - Figure 5.18Figure 5.18

Warm UpLoad DisturbancePID control with properly tunedPID + Fuzzy controlSet pointTemperatureTimeFigure 1.2 Fuzzy PIDEnhances ControlStabilityFigure 1

Strona 100 - UM93001C

Auto-tuningBeginsAuto-tuningBeginsAuto-tuningBeginsAuto-tuningBeginsAuto-tuningCompleteAuto-tuningCompleteAuto-tuningCompleteAuto-tuningCompletePID Co

Strona 101 - 100 ohms

3 20 Manual Tuning3 20 Manual TuningENDDoesthe processoscillate ?Doesthe processoscillate ?Doesthe processoscillate ?Issteady statereached ?Issteady s

Strona 102

The PBu is called the and the period of oscillation Tu is calledthe in the flow chart of Figure 3.23 . When this occurs, theprocess is called in a . F

Strona 103

PVTimeI actionI actionPerfectTI too lowTI too lowTI too highTI too highSet pointSet pointPVTimeD actionD actionPerfectTD too highTD too highTD too low

Strona 104 - Figure 7.1Figure 7.1

3 21 Signal Conditioner DC Power Supply3 21 Signal Conditioner DC Power SupplyThree types of isolated DC power supply are available to supply an exter

Strona 105

3 22 Manual Control3 22 Manual ControlThe manual control may be used for the following :purposesThe manual control may be used for the following :purp

Strona 106

3 23 Display Mode3 23 Display ModeOperationPress several times until ( Display ) appears on the display.Then press to enter the display mode. You can

Strona 107

3 24 Heater Current Monitoring3 24 Heater Current Monitoring3 25 Reload Default Values3 25 Reload Default ValuesA current transformer, CT94-1, should

Strona 108 - Fuzzy logic modified

Chapter 4 Programming the Full FunctionChapter 4 Programming the Full Function4 1 Event Input4 1 Event Input68UM93001CRefer to for wiring an event inp

Strona 109

UM93001C694 2 Second Set Point4 2 Second Set PointIn certain applications it is desirable to change the set point automaticallywithout the need to adj

Strona 110

AccessoriesCT94-1 = 0 - 50 Amp. AC Current TransformerOM95-3 = Isolated4-20mA/0-20mAAnalog Output ModuleOM95-4 = Isolated1-5V/0-5VAnalog Output Module

Strona 111

4 3 Second PID Set4 3 Second PID SetIn certain applications the process characteristics is strongly related to itsprocess value. The BTC-9300 provides

Strona 112

UM93001C714 4 Ramp&Dwell4 4 Ramp & DwellRampThe ramping function is performed during power up as well as any time the setpoint is changed. Cho

Strona 113

72UM93001COnce the timer output was energized it will remain unchanged until powerdown or an event input programmed for resetting alarm is applied.Onc

Strona 114

UM93001C734 5 Remote Set Point4 5 Remote Set PointSPMD selecting PV1 or PV2 will enable the BTC-9300 to accept a remote setpoint signal. If PV1 is sel

Strona 115

74UM93001C4 6 Differential Control4 6 Differential ControlIn certain applications it is desirable to control a second process such that itsprocess val

Strona 116

UM93001C754 7 Output Power Limits4 7 Output Power LimitsIn certain system the heater ( or cooler ) is over-designed such that theprocess is too heavil

Strona 117

76UM93001C4 8 Data Communication4 8 Data CommunicationTwo types of interface are available for Data Communication. These areand interface. Since RS-48

Strona 118

UM93001C774 9 Analog Retransmission4 9 Analog RetransmissionThe Analog Retransmission is available for model number BTC-9300-XXXXXNWhere N 3,4 or 5. S

Strona 119

78UM93001C4 10 Digital Filter4 10 Digital FilterIn certain application the process value is too unstable to be read. To improvethis a programmable low

Strona 120 - *B34, Error messages

UM93001C794 11 Sleep Mode4 11 Sleep ModeFUNC selects FULL to provide full function.SLEP selects YES to enable the sleep mode.Press for 3 seconds, the

Strona 121

FrontPanelRearTerminal1 3 Programming Port and DIP Switch1 3 Programming Port and DIP SwitchFigure 1.3 Access HoleOverviewFigure 1.3 Access HoleOvervi

Strona 122

80UM93001C4 12 Pump Control4 12 Pump ControlPump Control function is one of the unique features of BTC-9300. Using thisfunction the pressure in a proc

Strona 123

UM93001C81Programming Guide:Programming Guide:1. Perform auto-tuning to the system under such condition that the material( ie. pressure ) is exhausted

Strona 124

UM93001C5 1 Pump / Pressure Control5 1 Pump / Pressure ControlA regulated water supply system is widely used in residence, water plant,chemical plant,

Strona 125

UM93001CSet the following parameters in the setup menu:Set the following parameters in the setup menu:FUNC=FULLCOMM: optionalIN1=4-20IN1U=PUDP1=2-DPIN

Strona 126

5 2 VariablePeriodFullWaveSSR(VPFWSSR)5 2 Variable Period Full Wave SSR ( VPFW SSR )VPFW SSR is a variable period full wave solid-state relay. It can

Strona 127

UM93001CThe advantages of VPFW SSR over conventional SSR are summarized asfollowing table:The advantages of VPFW SSR over conventional SSR are summari

Strona 128

UM93001C5 3 Heat Only Control5 3 Heat Only ControlAn oven is designed to dry the products at 150 C for 30 minutes and thenstay unpowered for another b

Strona 129 - A 3 GlossaryA 3 Glossary

UM93001D5 4 Cool Only Control5 4 Cool Only ControlA BTC-9300 is used to control a refrigerator at temperature below 0 C. Toavoid the set point adjustm

Strona 130

UM93001C5 5 Heat-Cool Control5 5 Heat-Cool ControlAn injection mold required to be controlled at 120 C to ensure a consistentquality for the parts. An

Strona 131

UM93001D89The PID Heat-Cool is used for the above example.To achieve this set the following parameters in the Setup Menu:The PID Heat-Cool is used for

Strona 132

Alarm 1 IndicatorAlarm 1 IndicatorAlarm 2 / Output 2 IndicatorAlarm 2 / Output 2 IndicatorProcess Value IndicatorProcess Value IndicatorProcess Unit I

Strona 133

UM93001C5 6 Ramp&Dwell5 6 Ramp & DwellExample 1: Temperature cycling ChamberExample 1: Temperature cycling ChamberEIFN=SP.P2A1FN=TIMROUT1=REVR

Strona 134

UM93001C60 minutes60 minutes 60 minutes60 minutes60 C60 C 60 C60 C5 minutes5 minutes30minutes30minutes35minutes35minutes65 minutes65 minutes-10 C-10 C

Strona 135

5 7 Remote Set Point5 7 Remote Set PointUM93001CAn on-line multiple zone oven is used to dry paint. Since heat demand isvarious at different position

Strona 136 - A 4 IndexA 4 Index

UM93001C5 8 Differential Control5 8 Differential ControlIn certain applications it is desirable to control a second process such that itsprocess value

Strona 137

UM93001C5 9 Dual Set Point / PID5 9 Dual Set Point / PIDThe BTC-9300 will switch between the two PID sets based on the processvalue, the set point or

Strona 138

UM93001CA heat treating furnace is required to harden the mold at a high temperature (1000 C ) for 30 minutes, then the mold is cooled down with a pro

Strona 139

UM93001C5 10 RS-4855 10 RS-485A making plant has 5 production lines. Each production line is equippedwith 16 units of BTC-9300 to control the temperat

Strona 140

UM93001CEnters the setup mode to configure each BTC-9300. Choose FULL for FUNC,485 for COMM, RTU for PROT and select an unequal address ( ADDR ) for e

Strona 141 - A 6 WarrantyA 6 Warranty

UM93001C5 11 RS-2325 11 RS-232Suppose a chemical experiment is performed in a laboratory. And an engineerdesires to find out the relation between the

Strona 142

UM93001C5 12 Retransmit5 12 RetransmitAn air-conditioned room uses two units of BTC-9300 to control its temperatureand humidity. The temperature and h

Komentarze do niniejszej Instrukcji

Brak uwag